Specification of 3 phase uninterruptible power supply
Low Frequency 3 phase Online UPS | Three-phase- U-3310 |
Three-phase- U-3315 |
Three-phase- U-3320 |
Three-phase- U-3330 |
Three-phase- U-3340 |
Three-phase- U-3360 |
|
Rated capacity ( KVA/KW ) | 10/8 | 15/12 | 20/16 | 30/24 | 40/32 | 60/48 | |
Main Input | Phase | Three-phase five-wire (3L+N+PE) | |||||
Input Voltage (Vac) | 380/400/415 | ||||||
Voltage Range (Vac) | ±25% | ||||||
Frequency range (Hz) | 45~65 | ||||||
Power factor | >0.95 (with filter) | ||||||
Bypass Input | Phase | Three-phase five-wire (3L+N+PE) | |||||
Input Voltage (Vac) | 380/400/415 | ||||||
Voltage range (Vac) | +10%, +15%, +20% (can be set); -10%, -20%, -30% (can be set) | ||||||
Input Frequency (Hz) | 50 (60) +10% | ||||||
Output | Voltage (Vac) | 380/400/415 ±1% | |||||
Power factor | 0.8 | ||||||
Frequency (Hz) | Automatically track bypass frequency | ||||||
Waveform | Sine wave THDV less than 2% (pure linear load) | ||||||
Switching time (ms) | 0 ms | ||||||
Overall efficiency | ≥91% | ≥92% | |||||
Overload capacity | 105%~110%: 60min to bypass; 110%~125%: 10 min to bypass; 125%~150%: 1 min to bypass; >150%: 10s to bypass |
||||||
Battery | Battery voltage (Vac) | 384 (348 optional ) | 384 (348/360 optional ) | ||||
Environment | Operating temperature (°C) | -10~40 | |||||
Storage temperature (°C) | -25~55 (without battery) | ||||||
Relative humidity | 0~95% (no frosting) | ||||||
Working altitude | < 1500m, use derating according to GB/T3859.2 | ||||||
Noise (dB) | <55(1 meter from the device) | ||||||
Other features |
Alarm function | Output overload, mains abnormality, UPS failure, battery undervoltage, etc. | |||||
Protective function | Output short circuit, overload, over temperature, battery under voltage, output over and under voltage, fan failure alarm |
||||||
Communication function | Standard: RS232/RS485 Optional: SNMP/JBUS/MODBUS/Dry Contact |
||||||
Mechanical features |
Dimensions (W*D*H mm) | 300×600×810 | 400×750×1010 | 450×810 ×1160 |
|||
Net weight (kg) | 84 | 106 | 113 | 177 | 195 | 270 | |
Executive standard | YD/T1095-2017 |