Floor modular ups 25kva to 600kva

A floor-standing modular UPS system scalable from 25kVA to 600kVA, built on double-conversion online technology for continuous, uninterrupted power protection. Ideal for data centers, server rooms, and critical facility loads that need flexible, N+X redundant backup power with room to grow.

Category:

Floor modular UPS – 25kVA to 600kVA scalable power protection

This floor-mounted modular online UPS delivers reliable, high-density backup power for data centers, server rooms, industrial control systems, and other critical infrastructure. Built around a true double-conversion online design, it isolates connected equipment from voltage fluctuations, frequency variation, and power interruptions — keeping your critical loads running without interruption.

Key features


  • Flexible capacity range — scales from 25kVA up to 600kVA to match load requirements as they grow, without needing to replace the whole system.

  • Modular, hot-swappable design — individual power modules can be added, removed, or serviced without shutting down the load, minimizing maintenance downtime.

  • N+X redundancy — configurable redundancy options (such as 1:1 and 3:1) protect against single points of failure.

  • High power density — compact footprint saves valuable floor space compared to conventional UPS systems of similar capacity.

  • High efficiency operation — double-conversion efficiency and optional ECO mode reduce operating costs and heat output.

  • Real-time monitoring — continuous diagnostics on critical components, with fault logging and waveform recording to support fast troubleshooting.

  • Wide compatibility — supports 380V/400V/415V three-phase input/output, suited to a broad range of facility power standards.

  • Flexible battery configuration — adjustable battery string setup to match runtime and backup requirements.

Typical applications

  • Data centers and server rooms (small, medium, and large-scale)
  • Telecom and network infrastructure
  • Industrial control and automation systems
  • Offices, control rooms, and critical load facilities

Whether you’re deploying a new facility or expanding an existing power protection setup, this floor modular UPS platform offers a scalable path from 25kVA to 600kVA, letting you invest only in the capacity you need today while planning for future growth.

Model RM150/25C RM200/25C
System capacity 150kVA / 150kW 200kVA / 200kW
Power module capacity 25kVA / 25kW
Number of modules 6 8
Input
Configuration 3P+N+PE
Rated voltage 380/400/415VAC (line-line)
Rated frequency 50/60Hz
Input voltage range 304–478VAC (line-line) at full load; 228–304VAC with derating from 75% to 100% load
Input frequency range 40Hz – 70Hz
Input power factor > 0.99
Input THDi < 3% (100% linear load)
Bypass
Rated voltage 380/400/415VAC (line-line)
Rated frequency 50/60Hz
Input voltage range Settable, default -40% to +25%
Bypass frequency range Settable: ±1Hz, ±3Hz, ±5Hz
Bypass overload 110% for 1 hour; 125% for 10 min; 150% for 1 min; >150% for 200ms
Output
Rated voltage 380/400/415VAC (line-line)
Rated frequency 50/60Hz
Output power factor 1
Output THDu < 1% linear load; < 6% non-linear load (IEC/EN62040-3)
Inverter overload <110% for 1 hour; 110–125% for 10 min; 125–150% for 1 min; >150% for 200ms
Battery
Battery voltage ±240VDC
Charging accuracy 1%
Charging capacity Up to 20% of output power
Battery cold start Yes
Efficiency
AC mode > 96.0%
Battery mode > 95.5%
System
Display LED + LCD + touchscreen
Interface RS232, RS485, programmable dry contact
Options SNMP card, parallel operation, surge protection device
Environment
Operating temperature 0°C to 40°C
Storage temperature -40°C to 70°C
Relative humidity 0–95%, non-condensing
Noise (at 1 meter) 65dB at 100% load, 62dB at 45% load
Physical data
Module dimensions W×D×H (mm) 436 × 677 × 85
Module weight 18 kg
Cabinet dimensions W×D×H (mm) 485 × 900 × 1072 482 × 916 × 1550
Cabinet weight 140 kg 160 kg