Industrial Medical Online UPS 30KVA 3 Three Phase 50HZ 60HZ UPS Backup Power Supply

The RM-U-3330 Industrial Medical Online UPS is a robust 30KVA/24KW three-phase uninterruptible power supply designed for critical applications in industrial and medical environments. Featuring a three-phase five-wire input (380/400/415V ±25%) and output (380/400/415V ±1%), it ensures stable power delivery with a 0.8 power factor and ≥92% efficiency. With a pure sine wave output (THDV <2%), zero switching time, and advanced overload protection (up to 150% for 10 seconds), it guarantees reliable performance. Equipped with a 384V battery (348/360V optional), it supports seamless operation during power disruptions. The UPS includes RS232/RS485 communication (optional SNMP/JBUS/MODBUS) and operates in temperatures from -10°C to 40°C, making it ideal for demanding settings requiring uninterrupted power.
Categories: , Tag:
Low Frequency Online UPS RM-U-3310 RM-U-3315 RM-U-3320 RM-U-3330 RM-U-3340 RM-U-3360
Rated capacity (KVA/KW) 10/8 15/12 20/16 30/24 40/32 60/48
Main Input Phase Three-phase five-wire (3L+N+PE)
Input Voltage (Vac) 380/400/415
Voltage Range (Vac) ±25%
Frequency range (Hz) 45~65
Power factor >0.95 (with filter)
Bypass Input Phase Three-phase five-wire (3L+N+PE)
Input Voltage (Vac) 380/400/415
Voltage range (Vac) +10%, +15%, +20% (can be set); -10%, -20%, -30% (can be set)
Input Frequency (Hz) 50 (60) +10%
Output Voltage (Vac) 380/400/415 ±1%
Power factor 0.8
Frequency (Hz) Automatically track bypass frequency
Waveform Sine wave THDV less than 2% (pure linear load)
Switching time (ms) 0 ms
Overall efficiency ≥91% ≥92%
Overload capacity 105%~110%: 60min to bypass; 110%~125%: 10 min to bypass; 125%~150%: 1 min to bypass; >150%: 10s to bypass
Battery Battery voltage (Vac) 384 (348 optional) 384 (348/360 optional)
Environment Operating temperature (°C) -10~40
Storage temperature (°C) -25~55 (without battery)
Relative humidity 0~95% (no frosting)
Working altitude < 1500m, use derating according to GB/T3859.2
Noise (dB) <55 (1 meter from the device)
Other features Alarm function Output overload, mains abnormality, UPS failure, battery undervoltage, etc.
Protective function Output short circuit, overload, over temperature, battery under voltage, output over and under voltage, fan failure alarm
Communication function Standard: RS232/RS485,
Optional: SNMP/JBUS/MODBUS/Dry Contact
Mechanical features Dimensions (W*D*H mm) 300*600*810 400*750*1010 450*810*1160
Net weight (kg) 84 106 113 177 195 270
Executive standard YD/T1095-2017